OCP spec bars grid-fault dropouts; it doesn't bind utilities
(spec finalized September 17, made public at the summit October 12) A data-center power-grid spec whose original text lists Google, Meta, Microsoft and NVIDIA says data centers must not disconnect during grid faults within its defined range. We read the spec's original text (version 1.0.0) on OCP's site. It says large loads must "stay connected to the BES during all faults"; the BES is North America's bulk electric system. After a fault clears, computing equipment's power draw must "restore to 90% of pre-fault load within 2 seconds" (OCP spec original, 2026-09-17). Cooling equipment isn't covered by that rule. The power industry calls this kind of requirement ride-through. NVIDIA's blog describes it as returning to near full load within two seconds. The original says 90% of pre-fault load, and only for computing equipment. Our reading: on top of securing power, data centers are being asked to plan for staying connected when the grid faults. The spec doesn't give a reason for this rule. The next thing to watch is whether North American utilities or regulators write it into their interconnection requirements. The spec was written by four large power users themselves, not by utilities or regulators. It doesn't bind the utilities. How we checked →